This is PID Tuning software written in MS Excel that both hugely speeds up the tuning process and lets you learn the techniques in the blueprint on a simulation of your process. Make any beginner's mistakes in Excel - not on your plant, and be confident in your tuning before committing the new parameters to your controller. Pid tuner free download - PID, PiD Finder, PID Tracker, and many more programs. Entertainment Software MP3 & Audio Software Utilities & Operating Systems Drivers.
Free Version vs Full version |
PID LoopSim is the free version of PID LoopSim Pro. It supports most of the features available in the full version, with the following limitations:
Free version only supports self-regulating first order process. Full version supports self-regulating first order and second order process, and integrating process (tank level control).
Free version immplements the idel form of the PID equation only. Full version supports multiple forms of the PID equation (ideal form, series form and parallel form).
Free version includes ads. Full version is add-free.
Download and Install: |
PID LoopSim |
User Guide: |
1- Overview
Description of the control options:
Run: Start the process simulation
Pause: Pause the process simulation
Automatic: Switch the process to automatic mode.
Manual: Switch the process to manual mode.
Show Set Point control: Shows the slider to set the set point.
Show Manual output control: Shows the slider to set the PID output in manual mode.
Tuning Constants : Changes the P, I and D constant gains.
System Configuration : Opens the configuration screen to change the PID equation form, the process type and the process dynamics.
2- How to use PID LoopSim Pro
Initial setup:
Pid Tuning Rules
- In the configuration screen, click on Configure Process and select your type of process (1st order, 2nd order or integrating).
- Configure the dynamics of the process (lag time, dead time, etc).
- In the configuration screen, click on Configure PID Controller, then click PID Settings and enter maximum and minimum value of the process variable (in engineering units). This will set the maximum and minimum limits of the trend graphic, and the limits of the set point.
- Configure the PID equation form (ideal form, parallel form, or series form).
Test your process in manual mode:
- In the configuration screen, click on Start Simulation, to go to the simulation screen.
- Switch the control to manual mode by pressing Manual option.
- Open the manual control: click on 'Show Manual output control', a slider will pop-up. Touch the slider bar to the desire PID output value (0 to 100%).
- Touch the Run button to start the process. Enter different output values by touching the Manual Control slider, and see the response of the process.
Automatic mode:
- Open the menu and Tuning Constants. Enter the PID gains. You can change the units of the PID gains by touching them and selecting the new units.
- Touch Accept button to close the PID tuning window.
- Close the Manual Control slider and open the Set Point slider. Touch the Set Point slider to enter a new set point value. In the trend graphic, the green line will show the new set point.
- Touch 'Automatic' to switch the control to automatic mode.
- See the response of the process variable (yellow line). Make set point changes by touching the set point slider and see the response of the process.
3- Select the type of process and configure the process dynamics
PID LoopSim allows you to simulate three different type of processes:
A- First Regulating Process - 1st order:
Maximum PV: Steady state value of the process variable (in engineering units) when the PID controller output is 100%.
Minimum PV: Steady state value of the process variable (in engineering units) when the PID controller output is 0%.
Lag Time (TC) : Time constant of the process. 63.2% of process step response (see graphic below).
Dead Time (DT): Process delay (see graphic below).
B- First Regulating Process - 2nd order:
Maximum PV: Steady state value of the process variable (in engineering units) when the PID controller output is 100%.
Minimum PV: Steady state value of the process variable (in engineering units) when the PID controller output is 0%.
Lag Time 1 / Lag Time 2 (T1 and T2) : Time constants of the process (see graphic below).
Dead Time (DT): Process delay (see graphic below).
C- Integrating Process (tank level control):
Max Inflow Rate : Water flow rate (units: volume/minute) when the valve is 100% open.
Output Flow Rate : Flow rate of the water leaving the tank (see graphic below).
Dead Time (DT): Process delay (see graphic below).
4- Select the PID equation form
PID LoopSim supports three forms of the PID equation:
A- Ideal PID equation:
B- Parallel PID equation:
C- Series PID equation:
5- PID settings
Integral Anti-Windup: When enabled, the integral calculation suspends if the calculated output is outside the output high/low limits.
Bumpless Transfer: Enables output tracking and set point tracking, when in manual mode, to allow a smooth transfer from manual to automatic.
Pid Tuning Software Free Download Torrent
Source of Derivative: Select between derivative on error or derivative on process variable.
Max/Min PV Eng. Units : Maximum and minimum process variable engineering units for PID calculation. This values are used internally in the PID logic to calculate the error in percentage.
Output High/Low Limits : Maximum and minimum value of the output.
PID Control Action : Direct Control Action (Error = PV - SP) or Reverse Control Action (Error = SP - PV). Control action must be set to the opposite of the process action. E.g. for direct acting processes, use reverse control action.
6- PID rate
PID execution rate can be configured between 0.1 sec and 10 sec.
To change the PID execution rate go to Menu -> PID Controller -> PID rate
I've finally got my rig up and running, it's a 10 gal 240V system, currently RIMS but will be switching to HERMS. It was originally built by someone else for BrewTroller, but I switched to Brucontrol (zero regrets there). I'm running Brucontrol on a Mac with VirtualBox, it's working nicely.
I cannot figure out how to tune the PID algorithms. I've read all the background material, I've tried quite a range of values, and the system seems to consistently settle 30F above my target.
Here's the rig:
Here's the latest RIMS PID config:
And here is the result:
Any thoughts would be appreciated.
- Gregg
That is odd. Do you have an linear offset calibration set up anywhere in the sensor or PID?
I figured it out, I misconfigured the 1-wire temp sensors.
Currently viewing this topic 1 guest.
Latest Post: ESP32 issue Our newest member: daeconva44Recent PostsUnread Posts
Forum Icons: Forum contains no unread posts Forum contains unread posts Mark all read
Topic Icons: Not Replied Replied Active Hot Sticky Unapproved Solved Private Closed